4-76
.
Example 2: After one or more parameters in 00-41 ~ 00-56 are set, user parameters settings
are as follows.
Step
LCD Display
Descriptions
1
Select the start parameter group (03) in the advanced modes.
2
PARA 13
-06. Access Level
-07. Password 1
-08. Initialize
Press (READ/ ENTER) and
▲ (Up) / ▼ (Down) key to enter the
access level of parameter (13-06).
3
Edit 13-06
Access Level
---------------------------------------
1 User Level
(0~2)
< 2 >
Press (READ/ ENTER) key to enter the screen of the data setting/
read.
*
The selected setting value will flash.
4
─ADV─ G01-02
Access Level
1
User Level
(0-2)
< 2 >
Press
▲ (Up) / ▼ (Down) key to change setting value to 1 (13-06=1,
user level) and Press (READ/ ENTER) key to save the setting value
(03-00
).
Then, the digit stops flashing and the screen displays the
setting value. Few seconds later, the selected digit will flash again.
User level (13-06=1) can be set by one or more parameters in the
user parameters of 00-41 ~ 00-56. If users do not set user
parameters, 13-06 will not be set in the user level (setting value=1).
5
PARA 13
-06. Access Level
Press (DSP/FUN) key to the display of subdirectory.
6
Group
00.User Function
Press (DSP/FUN) key to the display of group directory. It is required
to press
▲ (Up) key to select Group 00 User Function.
7
Monitor
Freq Ref
12-16=000.00Hz
---------------------------------------
12-17=000.00Hz
12-18=0000.0A
Press (DSP/ FUN) key to enter the main screen. If user would like to
leave the screen of user parameters, press RESET key and then
DSP/FUN key to select parameter Group 13. Hotkeys are only
enabled in inverter software V1.12.
8
Group
00. User Function00 User
13.Driver Status
13-06 can be selected to be adjusted so leave parameters or enter
parameter group 00 to edit user parameters is allowable.
9
PARA 00
-41.
S1 Function Sel
Press (READ/ ENTER) key and
▲ (Up) / ▼ (Down) key to select
user parameter 0 (00-41) display.
10
Edit 00-41
S1 Function Sel
0
0
2-Wire
(FWD-RUN)
(00~57)
< 00 > < 03-00 >
Press (READ/ ENTER) key to enter the screen of data setting/ read.
*
The selected setting value will flash.
In this example, 03-00 (Multi-function terminal Function Setting-S1)
has been defined as user parameters (00-41). The right bottom
location displays the original parameter group.
Group
13 Driver Status
14 PLC Setting
15 PLC Monitor
Summary of Contents for F510 Series
Page 1: ......
Page 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...
Page 444: ...Ver 02 2019 09 ...