Group 08 Protection Parameters
08- 00
Stall Prevention Function
Range
【
xxx0b
】
:
Stall prevention is enabled in acceleration.
【
xxx1b
】
:
Stall prevention is disabled in acceleration.
【
xx0xb
】
:
Stall prevention is enabled in deceleration.
【
xx1xb
】
:
Stall prevention is disabled in deceleration.
【
x0xxb
】
:
Stall prevention is enabled in operation.
【
x1xxb
】
:
Stall prevention is disabled in operation.
【
0xxxb
】
: S
tall prevention in operation decelerates based on deceleration time 1
【
1xxxb
】
:
Stall prevention in operation decelerates based on deceleration time 2
08- 01
Stall Prevention Level in Acceleration
Range
【
20~200
】
%
08- 02
Stall Prevention Level in Deceleration
Range
【
330~410
】
V : 200V
【
660~820
】
V : 400V
08- 03
Stall Prevention Level in Operation
Range
【
30~200
】
%
08- 21
Limit of Stall Prevention in Acc over Base Speed
Range
【
1~100
】
%
08- 22
Stall Prevention Detection Time in Operation
Range
【
2~100
】
msec
Note: Stall prevention function only can be set in V/F control mode.
Stall prevention during acceleration (08-00=xxx0b)
(1) Prevents the inverter from faulting (Overcurrent, Motor overload, Inverter overload) when
accelerating
with heavy loads.
(2) When the inverter output current reaches the level set in parameter 08-01 minus 15% the acceleration
rate starts to decrease. When the inverter output current reaches the level set in parameter 08-01 the
motor stops accelerating.
(3) Reduce stall prevention level during acceleration (08-01) in case the motor stalls (when the motor
power is smaller than the inverter rating.
Stall prevention during acceleration (08-00=xxx0b)
Prevents the inverter from faulting (Overcurrent, Motor overload, Inverter overload) when accelerating with
heavy loads.
When the inverter output current reaches the level set in parameter 08-01 minus 15% the acceleration rate
starts to decrease. When the inverter output current reaches the level set in parameter 08-01 the motor
stops accelerating. Refer to Fig.4.3.57 for more information.
Notes:
- Reduce stall prevention level during acceleration (08-01) in case the motor stalls (when the motor power
is smaller than the inverter rating.
- The inverter rated output current should be set to 100%.