6-6
6.4 Reference from two Analog Inputs
Analog input AI1 is used as master frequency reference and analog input AI2 is used as auxiliary
frequency reference.
Analog Reference AI1: 0
– 10 V (Setting 00-05 = 1)
Analog Reference AI2: 0
– 10 V (Setting 00-06 = 1, 04-05 = 1)
AI1
– Analog Input 1
AI2
– Analog Input 2
04-00 Setting
(Default = 1)
Dipswitch SW2
(Default ‘V’)
0 ~ 10V
0 ~ 10V
0
Set to ‘V’
0 ~ 10V
4 ~ 20mA
1
Set to ‘I’
(S+)
(S-)
S1
S3
S5
24V
+10V
MT
GND
GND
AI1
AI2
E
24VG
S2
S4
S6
F1
F2
PO
PI
AO1
AO2
E
Connect sh ield to
co ntrol grou nd terminal
0
– 10 V
+
-
Analog Input AI1
Common/0V, GND
Control Terminals /
User Terminals
Analog Input AI2
+
6.5 Change Frequency Unit from Hz to rpm
Enter the number of motor poles in 16-03 to change the display units from Hz to rpm.
16-03
Display unit
Range
0:
Display unit is Hz (Resolution is 0.01Hz)
1:
Display unit is % (Resolution is 0.01%)
2:
Rpm display; motor rotation speed is set by the control modes to select IM (02-07)/ PM
(22-03) motor poles to calculate
3~39:
Reserved
40~9999:
100% is XXXX with no decimals (integer only)
10001~19999:
100% is XXX.X with 1 decimal
20001~29999:
100% is XX.XX with 2 decimals
30001~39999:
100% is X.XXX with 3 decimals
Example:
Motor poles 4, 02-07 or 22-03 = 4.