4-114
03-15
Current Agree Level
Range
【
0.1~999.9
】
A
03-16
Delay Time of Current Agree Detection
Range
【
0.1~10.0
】
Sec
03-53
Current Agree Level 2
Range
【
0.0~999.9
】
A
Note: The Maximum Value of 03-53 will be limited by Setting Value of 03-15
03-11=13: Relay is active when output current is larger than that in 03-15.
03-15: The suggested setting value is 0.1~ the motor rated current.
03-16: The unit of the setting value (0.1~10.0) is second.
In addition, when the Output Current is ≤
03-53,
the delay time of relay signal from ON to OFF is 100ms (constant).
Timing Diagram:
03-16
固定
100msec
03-15
03-11
繼電器
ON
I
負載電流
100%
T
03-53
03-48
Low Current Detection Level
Range
【
0.1~999.9
】
A
03-49
Low current Detection Delay Time
Range
【
0.00~
655.34
】
Sec
03-11 =57: Relay is active when output current is lower than that in 03-48.
03-48: Setting value: 0.1~999.9; when it is 0.0, function of low current detection is disabled.
03-49: Setting value: 0.00~655.35 (unit: sec); when the current is continuously lower than the setted
value of parameter 03-48 within the setted time of parameter 03-49, the relay is enabled. The delay
time of relay signal from ON to OFF is 100ms (constant).