4
-
288
24- 09
Frequency/ Target Switch
Range
【
0
】
Disable
【
1
】
Enable
24- 10
Stop Mode Selection on Mode 6/7/9
Range
【
0
】
Disable
【
1
】
Enable
When 24-09=0, action of reducing pump starts from the output frequency after PID control agreeing the
level of lower limit frequency and the delay time of lower limit frequency.
When 24-09=1, action of reducing pump starts when PID feedback (12-39)>PID setting (12-38).
When 24-10=1, all relays disconnect at stop and first relay starts to run at operation.
Note: 24-10 is enabled only when 24-00=6, 7, 9.
24- 17
Increase and Decrease Pump Interval PID Control
Range
【
0
】
Increasing / Decreasing Pump Section without PID Control
【
1
】
Increasing / Decreasing Pump Section with PID Control
24-17=0: When increasing / decreasing the pump, in order to balance the current water usage, the Inverter
will decelerate to the Frequency Lower Limit when increasing the pump, conversely, the Inverter will
increase to Frequency Upper Limit when decreasing the pump, then the Inverter will switch back to the
speed required by the PID Control.
24-17=1: When using water at the extreme switch when increasing / decreasing the pump, and in order to
balance the water usage, the Inverter Increasing / Decreasing Pump All Sections can be selected to use
PID to control the Inverter Speed.
24- 11
High Pressure Limit Level
Range
【
0~10000
】
24- 14
Low Pressure Limit Level
Range
【
0~10000
】
24-11
High Pressure Limit Level
:
When pressure feedback value is higher than the set value of highp pressure limit level, the alarm signal
occurs and then inverter stops the operation.
24-14
Low Pressure Limit Level
:
When pressure feedback value is lower than the set value of low pressure limit level, the alarm signal
occurs and then inverter stops the operation.
User can refer to the setting of 10-00=4 to set the value of parameters 24-11& 24-14. Revise the upper
limit value by the setting of parameter 10-33, determine the decimal position by adjusting the setting of
parameter 10-34, and the unit display by parameter 10-35.
Summary of Contents for F510 Series
Page 1: ......
Page 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...