4-23
Group 07: Start /Stop Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
07-00
Momentary Power Loss/ Fault
Restart Selection
0: Disable
0
-
O
O
O
1: Enable
07-01 Fault Auto-Restart Time
0~7200
0
s
O
O
O
07-02
Number of Fault Auto-Restart
Attempts
0~10
0
-
O
O
O
07-03
Reserved
07-04 Direct Start at Power on
0: When the external run command
is enabled, direct start at power
up
0
-
O
O
O
1: When the external run command
is enabled, unable to direct start
at power-up.
07-05
Automatic start delay at
power up
1.0~300.0
3.5
Sec
O
O
O
07-06
DC Injection Braking Start
Frequency
0.0~10.0
0.5
Hz
O
O
O
07-07 DC Injection Braking Current 0~100
50
%
O
O
O
07-08
DC Injection Braking Time at
Stop
0.00~10.00
0.50
s
O
O
O
07-09 Stop Mode Selection
0: Deceleration to Stop
0
-
O
O
O
1: Coast to Stop
O
O
O
2: DC Braking Stop
O
O
X
3: Coast to Stop with Timer
O
O
O
07-10
~
07-12
Reserved
07-13 Low Voltage Detection Level
200V: 150~300
190
V
O
O
O
400V:
300~600
380
07-14 Pre-excitation Time
0.00~10.00
2.00
s
X
O
X
07-15 Pre-excitation Level
50~200
100
%
X
O
X
*6
07-16
DC Injection Braking Time at
Start
0.00~100.00
0.00
s
O
O
O
07-17
Reserved
07-18 Minimum Base block Time
0.1~5.0
-
Sec
O
O
O
07-19
Direction-Detection Speed
Search Operating Current
0~100
50
%
O
O
X
07-20
Speed Search Operating
Current
0~100
20
%
O
O
X
07-21
Integral Time of Speed
Searching
0.1~10.0
2.0
Sec
O
O
X
07-22
Delay Time of Speed
Searching
0.0~20.0
0.2
Sec
O
O
X
07-23 Voltage Recovery Time
0.1~5.0
2.0
Sec
O
O
X
07-24
Direction-Detection Speed
Search Selection
0: Disable
1
-
O
O
X
1: Enable
07-25 Low voltage Detection Time
0.00~1.00
0.02
Sec
O
O
O
07-26 SLV Speed Search Function 0: Enable
0
-
X
O
X