4
-
181
10- 03
PID
Control Mode
Range
【
xxx0b
】:
PID Disable
【
xxx1b
】:
PID Enable
【
xx0xb
】:
PID Positive Characteristic
【
xx1xb
】:
PID Negative Characteristic
【
x0xxb
】:
PID Error Value of D Control
【
x1xxb
】:
PID Feedback Value of D Cotrol
【
0xxxb
】:
PID Output
【
1xxxb
】:
PID
Frequency Command
PID target value source setting(10-00) / PID feedback value source setting(10-01)
Please confirm parameter 04-00 conform the need (0V~10 V or
4mA~20 mА) if AI2 as PID target or PID
feedback. And
check the dip switch
from control board to the input type (V or I), please refer to wiring
diagram for more detail.
When 10-03 is set to xxx0b, PID will is disabled; if it is set to xxx1b, PID is enabled.
Note:
-
LCD keypad will be switched automatically (16-00).
-
Main Screen Monitoring will be changed to PID Setting (12-38).
-
Sub-Screen Monitoring 1 will be changed to PID Feedback (12-39).
-
Sub-Screen Monitoring 2 will be changed to Output Frequency (12-17).
At this time, if the setting is disabled, it will be switched automatically back to frequency command as the
main page. When switching to PID setting in the LED keypad, it displays the modes selection of parameter
23-05.
Note
: when 23-05=0, set the value in the conditions of 10-33 < 1000 and 10-34=1, or the inverter will
display the signal of PID setting error (SE05).
When 10-03 is set to xx0xb, PID output occurs forward;
When 10-03= xx1xb
: PID output is reverse. PID output is chosen to reverse, If PID input is
negative
, the
output frequency of PID will gain.
On the contrary,
When 10-03 is set to x1xxb, PID control for feedback differential value is enabled; if it is set to x0xxb, basic
PID control is enabled. Refer to Fig.4.3.69 and Fig.4.3.70.
When 10-03 is set to 0xxxb, PID output is enabled and it is corresponding to the frequency of 01-02 at
100%.
When 10-03 is set to 1xxxb, PID output and frequency command are enabled. The output percentage of
frequency command (corresponding to the selected main frequency command of 00-05/ 00-06) will be
cumulated when the inverter starts to run, and PID control starts.
10- 04
Feedback Gain
Range
【
0.01~10.00
】
10- 05
Proportional Gain (P)
Range
【
0.00~10.00
】
10- 06
Integral Time (I)
Range
【
0.0~100.0
】
Sec
10- 07
Differential Time (D)
Range
【
0.00~10.00
】
Sec
10- 09
PID Bias
Range
【
-100~100
】
%