3-27
Table 3.3.4.2 Description of control circuit terminals (Continued)
Type
Terminal
Terminal function
Signal level/ information
Relay
output
R1A-
R1B-
R1C
Relay A contact (multi-function output terminal)
Relay B contact (multi-function output terminal)
Relay contact common terminal, please refer to
parameter group 03 in this manual for more functional
descriptions.
Rating:
250Vac: 10 mA ~ 1A
30Vdc: 10 mA ~ 1A
R2A-R2C With the same functions as R1A/R1B/R1C
Rating:
250Vac: 10 mA ~ 1A
30Vdc: 10 mA ~ 1A
R3A-R3C With the same functions as R1A/R1B/R1C
Safety
input
F1
On: normal operation.
Off: emergency stop.
(Jumper wired has to be removed to use external safety
function to stop.)
24Vdc, 8mA, pull-high
F2
Safety command common terminal
24V Ground
RS-485
port
S (+)
RS485/MODBUS
differential input and output
S (-)
Grounding
E (G)
Grounding to earth
Shield the connecting terminal
----
Notes:
*1:
Multi-function digital input can be referred to in this manual.
- Group 03: External Terminals Digital Input / Output Function Group.
*2:
Multi-function analog input can be referred to in this manual.
- Group 04 - External Terminal Analog Signal Input (Output) Function Group.
*3:
Multi-function analog output can be referred to in this manual.
- Group 04 - External Terminal Analog Signal Input (Output) Function Group.
Caution
Maximum output current capacity for terminal 10V is 20mA.
Multi-function analog output AO1 and AO2 are for use for an analog output meter. Do not
use these output for feedback control.
Control board’s 24V and 10V are to be used for internal control only. Do not use the
internal power-supply to power external devices.