4-54
Group 22: PM Motor Parameters-
only available when PM Control Mode is selected
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
22-22
Fault History of SLV PM Motor
Tuning
0. No Error
0
--
X
X
O
*4
1~4: Reserved
5: Circuit tuning time out.
6: Reserved
7: Other motor tuning errors
8: Reserved
9: Current Abnormity Occurs while
Loop Adjustment.
10: Reserved
11: Stator Resistance
Measurement Timeout
12: Reserved
22-25
Detection Mode Selection of
Default Magnetic Pole
0: Angle before Stop
2
(Note8)
-- X X
O
Note4
1: Mode 1
2: Mode 2
22-26 Estimator Mode
0~1 (in PMSLV mode)
0
-
X
X
O
Note6
22-27 Mode 2 Voltage Command
5~
120
(Note8)
(22-25=2 or 22-26=1is
enabled)
50
%
X
X
O
Note4
22-28
Mode 2 Frequency Division
Ratio
0~8
(Note8)
(22-25=2 or 22-26=1is
enabled)
2
X
X
O
Note4
22-29
Field-Weakening Voltage
Control
80~
110
(Note8)
100
%
X
X
O
Note4
22-30
SPM Speed Estimation Gain
1~100
85
%
X
X
O
Note6
22-31
SPM Speed Estimation Filter
Value
1~2000
60
HZ
X
X
O
Note6
22-32 MTPA Selection
0: Disable
0
-
X
X
O
Note8
1: Mode 1
22-33 MTPA Gain
0~400%
200
%
X
X
O
Note8
22-34 IPM Estimator Gain
0.1~500.0
180
-
X
X
O
Note8
Group 23 Pump & HVAC Function Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
23-00 Function Selection
0: Disable
0
-
O
O
O
1: Pump
2: HVAC
3: Compressor *7
23-01
Setting of Single & Multiple
Pumps and Master & Slave
Machines
0: Single Pump
0
O
O
O
1: Master
2: Slave 1
3: Slave 2
4: Slave 3
23-02 Operation Pressure Setting
0.10 ~ 650.00
4.00
PSI
O
O
O
*6
23-03
Maximum Pressure of
Pressure Transmitter
0.10 ~ 650.00
10.00 PSI
O
O
O
*6