219
set for 3-wire start operation and stop command.
Inverter input voltage (01-14) is automatically set to 230V (200V class) or 415V (400V class).
When 01-00 (V/F curve) set to F, Inverter maximum frequency (01-12) is automatically set to 50Hz.
13-08=6:
2-wire initialization (200V/380V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to Fig.4.3.1.
Inverter input voltage (01-14) is automatically set to 200V (200V class) or 380V (400V class).
When 01-00 (V/F curve) set to F, Inverter maximum frequency (01-12) is automatically set to 50Hz.
13-08=7:
3-wire initialization (200V/380V)
Multi-function digital input terminal S5 controls the forward / reverse direction, and terminals S1 and S2 are
set for 3-wire start operation and stop command.
Inverter input voltage (01-14) is automatically set to 200V (200V class) or 380V (400V class).
When 01-00 (V/F curve) set to F, Inverter maximum frequency (01-12) is automatically set to 50Hz.
13-08=8:
PLC initialization
Clear built-in PLC ladder logic and related values.
13-08=9: 2 wire initialization (230V/460V, 60Hz)
– FACTORY DEFAULT
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to Figure 4.3.1. The input voltage (01-14) will be
set to 230V (200V class) or 460V (400V class) automatically and when 01-00 (V/F curve) is set to F,
the maximum frequency of 01-12 will be set to 60Hz automatically.
13-08=10: 3 wire initialization (230V/460V, 60Hz)
– FACTORY DEFAULT
Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1
and S2 are set for 3-wire start operation and stop command. Refer to Figure 4.3.2 and Figure 4.3.3
for 3-wire type operation mode. The input voltage (01-14) will be set to 230V (200V class) or 460V
(400V class) automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of 01-12
will be set to 60Hz automatically.
13-08=11:
2 wire initialization (230V/400V, 60Hz)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to Figure 4.3.1. The input voltage (01-14) will be set to 230V (200V class)
or 400V (400V class) automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of
01-12 will be set to 60Hz automatically.
13-08=12:
3 wire initialization (230V/460V, 60Hz)
Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are
set for 3-wire start operation and stop command. Refer to Figure 4.3.2 and Figure 4.3.3 for 3-wire type
operation mode. The input voltage (01-14) will be set to 230V (200V class) or 400V (400V class)
automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of 01-12 will be set to 60Hz
automatically.