7-1
Chapter 7 Operation Method Configuration (Run / Stop)
The inverter offers users several choices to run and stop from different sources. The most commonly
used methods are described in the next sections.
Operation command is selected with parameter 00-02.
00-02: Run Command Selection
This function sets the frequency command source.
Setting Range:
0 to 3
To set parameter 00-01:
- After power-up press the
DSP/FUN
key
- Select
00 Basic Fun
- Press
READ/ ENTER
key
- Select parameter -01
with the
UP/DOWN
▲ and ▼ keys and press the
READ/ ENTER
key.
In the parameter list move cursor to 00-01 with the
UP/DOWN
keys and press
READ/ ENTER
key to
select.
00-02
Run Command Selection
Range
0:
Keypad control
1:
External terminal control
2:
Communication control
3:
PLC
4:
RTC
7.1 Run/Stop from the Keypad (00-02=0)
– Default Setting
Use the
RUN
key to run the drive in forward direction and the
FWD/REV
key to change the motor direction. (Note: to disable
reverse direction set parameter 11-01 to 1)
Press
STOP
key to stop the inverter. (Note: Stop method can be set
with parameter 07-09, default is
deceleration to stop)
.
Fref Ref
12-16=005.00Hz
Monit or
12-17=000.00Hz
12-18=0000.0A