4-109
t
t
ON
OFF
01-08(Fmin)
Output
Frequency
Zero
Speed
Figure 4.3.23 Zero-speed operation
03-1X=21:
Inverter Ready
Output is active when no faults are active and the inverter is ready for operation.
03-1X=22:
Undervoltage Detection
Output is active when the DC bus voltage falls below the low voltage detection level (07-13).
03-1X=23:
Source of operation command
Output is active in local operation command.
OFF
Remote mode:
00-02 = 1 or 2, or any one of the multi-function digital input terminals (S1 to S6) set to
function 5 (LOCAL / REMOTE control) is OFF.
SEQ LED of the keypad is ON.
ON
Local mode:
00-02 = 0, or any one of the multi-function digital input terminals (S1 to S6) set to
function 5 (LOCAL / REMOTE control) is active.
SEQ LED of the keypad is OFF.
03-1X=24:
Source of frequency command
Output is active in local frequency command.
OFF
Remote mode:
00-05 = 1 or 2, or any one of the multi-function digital input terminals (S1 to S6) set to
function 5 (LOCAL / REMOTE control) is OFF.
REF LED of the keypad is ON.
ON
Local mode:
00-05 = 0, or any one of the multi-function digital input terminals (S1 to S6) set to
function 5 (LOCAL / REMOTE control) is active.
REF LED of the keypad is OFF.
03-1X=26:
Frequency reference missing
Output is active when the frequency reference is lost. When parameter 11-41 is set to 0 the inverter will
decelerate to a stop. When parameter 11-41 is set to 1 operation will continue at the value of parameter
11-42 times the last know frequency reference.
03-1X=27:
Time function output
Output is controlled by timer function see parameter 03-37 and 03-38.
03-1X=32:
Communication control contacts