10-5
LED display
Description
Cause
Possible solutions
OPBFT
High pressure
fault
High pressure fault
Since feedback value of pump
pressure is lower than limit of
maximum flow.
Check feedback signal is
correct.
Check if feedback value of
pressure is lower than limit of
maximum pressure (23-12).
LSCFT
Low suction fault
Low suction fault
Insufficient water supply of effluent
channel leads to insufficient suction
PID difference is higher than its
level or current is lower than output
current level
Check if water of effluent
channel is enough, and
water supply is regular.
Check PID difference is
higher than its level or
current is lower than output
current level
CF00
Operator
Communication
Error
Errors of data transmission
occur in keypad
Keypad and inverter cannot
transmit data after power on 5
seconds
Disconnect the operator and
then reconnect.
Replace the control board
CF01
Operator
Communication
Error 2
Errors of data transmission
occur in keypad
Keypad and inverter can transmit
data but transmission error occurs
for more than 2 seconds
Disconnect the operator and
then reconnect.
Replace the control board
CT Fault
Fault occurs in voltage level
of three-phase input
Abnormal input voltage, too much
noise or malfunctioning control
board
Check input voltage signal
and the voltage on the control
board.
Double
Communication
Error
Redundant Profibus and
Modbus protocol
User may use two communication
mechanisms simultaneously
Check only one
communication mechanism is
used.
PTC Signal
Loss
PTC Signal Loss detecting
triggers error message
PTC connection trips and has
lasted for more than 10 seconds
Check if MT terminal and
GND terminal are connected.
OPR
Disconnection
Run command is set to
keypad mode (00-02=0).
But when the inverter runs,
the operator is
disconnected. Selection of
operator removed (16-09)
determines if the inverter
stops or displays fault
signal.
The inverter runs at keypad mode
(00-02=0), but warning of operator
being disconnected/ removed
occurs.
Check if the operator is
disconnected or removed.
FBLSS
PID Feedback
Signal Loss
When 23-19 > 0, the
inverter will display fault
signal on the basis of the
value of feedback pressure
< operation pressure setting
(23-02) x detection
proportion of loss pressure
(23-19) and detection time
of loss pressure (23-18)
passed, and 23-78=2
in the
meanwhile.
Since proportion of loss pressure
(23-19) is enabled and over high,
the inverter trips to fault. Thus,
feedback sensor cannot operate
properly or is not installed correctly.
Check if the proportion of loss
pressure (23-19) is set
correctly.
Make sure the feedback
sensor is installed correctly
and PID feedback signal
operates normally.
SC
Short Circuit
The inverter output or load
is at short circuit.
Short circuit or grounding fault
(08-23=1) occurs from the damage
to motor, insulation deterioration or
cable breakage.
Check if the load is at correct
wiring.
PF
Protection
OH1 error occurs for 3
times in 5 minutes when
Run command in multi-function
digital input terminals is not
Remove run command in
multi-function digital input