4-106
Value
Function
Description
Control Mode
Name
LCD Display
V/F SLV
PM
SLV
6
Automatic
Restart
Auto Restart ON: the period of automatic restart
O
O
O
7~8 Reserved
Reserved
Reserved
-
-
-
9
Baseblock
Baseblock
ON: During baseblock
O
O
O
10~11 Reserved
Reserved
Reserved
-
-
-
12
Over-Torque
Detection
Over Torque ON: Over torque detection is ON
O
O
O
13
Current Agree
Current Agree ON: Output current > 03-15
O
O
O
14
Mechanical
Brake Control
(03-17~03-18)
Mechanical
Brake Control
ON: Mechanical brake release frequency
OFF: Mechanical brake operation frequency
O
O
O
15~17 Reserved
Reserved
Reserved
-
-
-
18
PLC Status
PLC
statement
ON: when 00-02 is set to 3 (PLC operation
command source)
O
O
O
19
PLC Control
Control From
PLC
ON: Control from PLC
O
O
O
20
Zero Speed
Zero Speed
ON: Output frequency < Minimum output
frequency (Fmin)
O
O
O
21
Inverter Ready
Ready
ON: Inverter ready (after power on, no faults)
O
O
O
22
Undervoltage
Detection
Low Volt
Detected
ON: DC bus voltage = < Low-voltage warning
detection level (07-13)
O
O
O
23
Source of
Operation
Command
Run Cmd
Status
ON: Operation command from LED digital
operator (local mode)
O
O
O
24
Source of
Frequency
Command
Freq Ref
Status
ON: Reference frequency from LED digital
operator (local mode)
O
O
O
25
Low Torque
Detection
Under Torque ON: Low-torque detection is ON
O
O
O
26
Frequency
Reference
Missing
Ref. Loss. ON: Reference frequency loss
O
O
O
27
Timing Function
Output
Timer Output
Set time function parameter to 03-37 and
03-38
,
and the time function input is set by
parameter from 03-00 and 03-05
O
O
O
28~31 Reserved
Reserved
Reserved
-
-
-
32
Communication
Control
Contacts
Control
From Comm
ON: DO is set by communication control.
O
O
O
33
RTC Timer 1
RTC Timer 1
ON: 16-36 (RTC Speed Selection) selects
Timer 1 and 16-32 (Source of Timer 1) is
active in the set time.
O
O
O
34
RTC Timer 2
RTC Timer 2
ON: 16-36 (RTC Speed Selection) selects
Timer 2 and 16-33 (Source of Timer 2) is
active in the set time.
O
O
O
35
RTC Timer 3
RTC Timer 3
ON: 16-36 (RTC Speed Selection) selects
Timer 3 and 16-34 (Source of Timer 3) is
active in the set time.
O
O
O
36
RTC Timer 4
RTC Timer 4
ON: 16-36 (RTC Speed Selection) selects
Timer 4 and 16-35 (Source of Timer 4) is
active in the set time.
O
O
O
37
Detection
Output of PID
Feedback Loss
PID Fbk Loss ON: PID Feedback Loss
O
O
O