4-34
Group 11: Auxiliary Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
11-49
~
11-50
Reserved
11-51
Braking Selection of Zero
Speed
0: Disable
0
-
O
X
X
1: Enable
11-52
~
11-53
Reserved
11-54
Initialization of Cumulative
Energy
0: Do not Clear Cumulative Energy
0
-
O
O
O
*1
1: Clear Cumulative Energy
11-55 STOP Key Selection
0: Stop Key is Disabled when the
Operation Command is not
Provided by Keypad.
1
-
O
O
O
1: Stop Key is Enabled when the
Operation Command is not
Provided by Keypad.
11-56 UP/DOWN Selection
0: When UP/DOWN in Keypad is
Disabled, it will be Enabled if
Pressing ENTER after
Frequency Modification.
0
-
O
O
O
1: When UP/DOWN in Keypad is
Enabled, it will be Enabled upon
Frequency Modification.
11-57
Reserved
11-58 Record Reference Frequency
0: Disable
0
-
O
O
O
*1
1: Enable
11-59 Gain of Preventing Oscillation
0.00~2.50
0.05
O
X
X
*7
11-60
Upper Limit of Preventing
Oscillation
0~100
100
%
O
X
X
*7
11-61
Time Parameter of
Preventing Oscillation
0~100
0
O
X
X
*7
11-62
Prevention of Oscillation
Selection
0: Mode 1
1: Mode 2
2: Mode 3
1
O
X
X
*7
11-63 Flux-Strengthening Selection
0: Disable
1
X
O
X
Note1
1: Enable
11-64
Acceleration Speed Gain
Adjustment
0.1~10.0
1.0
-
O
X
X
Note3
11-65 Target Main Circuit Voltage
200V: 200V~400V
370
-
O
X
X
Note3
400V: 400V~800V
740
11-66
2 Phase/ 3 Phase PWM
Switch Frequency
6.00~60.00
20
Hz
O
O
X
Note3
11-67
Detection Range at Soft PWM
Function 2
0~12000
0
Hz
X
O
O
Note3
11-68
Detecting Start Frequency at
Soft PWM Function 2
6.00~60.00
20
Hz
X
O
O
Note3
11-69 Gain of Preventing Oscillation 0.00~200.00
5.00
%
O
X
X
Note2
Summary of Contents for F510 Series
Page 1: ......
Page 434: ...11 10 Dimensions of LED LCD keypad IP20 Figure 11 5 2 Dimensions of LED keypad ...
Page 444: ...Ver 02 2019 09 ...