5-18
5-3-8 Speed Loop Gain
In speed mode there are two speed controller loops,
with separate Gain ( P) and Integral (I) functions.
Speed controllers 1 or 2 can be selected by setting one of the multi- function input terminals,
to selection G-SEL or by setting one of the parameters Cn20-Cn24 as required.
Please refer to section 5-3-11 section B for more details.
Parameter
Name
Default
Unit
Setting range
Control
mode
Sn211
Speed loop gain 1
40
Hz
10~450
Pe/Pi/S
Sn212
Speed loop integral time constant 1
100
x0.2
ms
1~500 Pe/Pi/S
Sn213
Speed loop gain 2
40
Hz
10~450
Pe/Pi/S
Sn214
Speed loop integral time constant 2
100
x0.2
ms
1~500 Pe/Pi/S
Diagram below shows the speed controller.
Setting a high speed loop gain or a lower speed loop integral time provides a faster speed control response
time.
For more details refer to section
5-5
.
Kv: Speed Loop Gain (Hz)
S
T
1
1
K
i
v
Ti: Speed Loop Integral
Time Constant (sec)
Summary of Contents for TSTA Series
Page 1: ......
Page 12: ...1 6 1 4 2 Direction and Distance Fan Fan ...
Page 15: ......
Page 45: ......
Page 59: ......
Page 69: ......
Page 175: ......
Page 206: ...9 4 Dimension for TSTA 15 and TSTA 20 ...
Page 207: ...9 5 Dimension for TSTA 30 ...
Page 208: ...9 6 Dimension for TSTA 50 and TSTA 75 ...
Page 211: ...DIMENSION TSB 07 08 SERIES 9 9 ...
Page 214: ......
Page 215: ......
Page 218: ......