5-74
Circuit diagram for analog monitor shows below:
Analog monitor output zero offset can be adjusted by parameters
Cn027&Cn028
as below.
Parameter
Name
Default
Unit
Setting Range
Control Mode
Cn027
Analog Monitor 1
Offset adjustment
4 x40mV -250~250 ALL
Cn028
Analog Monitor 2
Offset adjustment
4 x40mV -250~250 ALL
Analog Monitor
Output Voltage (V)
Adjusting Value for
Bias Voltage
Time
5-6-10 Factory setting parameter
This parameter can reset all parameter settings to default value (factory reset).
Parameter
Signal
Name Setting
Description
Control
Mode
0 Disabled
★
Cn029 Reset
parameters
1
All parameters are reset to default values.
ALL
New setting will become effective after re-cycling the power.