User Manual of SY5000 series AC Drive Parameter instrction
~53~
5.2 Parameter instruction
Function code of basic function (group b)
b-000 setting frequency by panel number
When all parameters of b-002 jog operation, b-003 multi-step speed running,
b-004 voltage input selection, b-005 current input selection, b-006 panel
potentiometer selection and b-007 pulse frequency given simultaneously choose
0
(
disabled
)
, the inverter runs according this setting frequency. At this moment,
enter setting state of parameter b-000 panel number setting
frequency, click
keys and immediately modify oprating frequency of the inverter.
(
):
increasing frequency
;(
)
: decreasing frequency
b-001 panel selection
Used to select RUN / STOP keys are enabled.
b-001
Corresponding function
0
Run, stop, and motional direction of the motor all are
determined by b-036, b-035 is disabled.
1~4
When setting terminals (1~4 correspond to PI1 ~ PI4) are
short-circuiting with COM, run and stop are controlled by
RUN/STOP keys, motional direction of the motor at this
moment is determined by b-035.
5
Run and stop of the motor is controlled by RUN/STOP keys,
motional direction of the motor at this moment is determined
by b-035.
b-002 jog command
b-027 jog frequency
b-028 jog accel/decel mode
b-029 jog accel time
b-030 jog decel time