User Manual of SY5000 series AC Drive Parameter instrction
~66~
E-021 multi-step speed switching 3
E-022 multi-step speed setting 1
E-023 multi-step speed setting 2
E-024 multi-step speed setting 3
E-025 multi-step speed setting 4
E-026 multi-step speed setting 5
E-027 multi-step speed setting 6
E-028 multi-step speed setting 7
E-029 each step speed accel/decel time selection
When b-003 = 1, set frequency by terminal state combination which is selected
by E-019, E-020
、
E-021. There are 8 state combination, respectively corresponds
to 1~8 steps speed. (As shown in the following table, 1 represents short-circuiting
between corresponding terminal and COM, 0 represents disconnection between
corresponding term
inal and COM.
E-021
E-020
E-019
Corresponding running section
0
0
0
Default frequencies
(
b-004=0
:
panel potentiometer setting frequency
;
b-004=5: external potentiometer setting frequency
)
0
0
1
Step 1
(
E-022
)
0
1
0
Step 2
(
E-023
)
0
1
1
Step 3
(
E-024
)
1
0
0
Step 4
(
E-025
)
1
0
1
Step 5
(
E-026
)
1
1
0
Step 6
(
E-027
)
1
1
1
Step 7
(
E-028
)
When set b-003 as 2 or 3, No.1~ 4 step speed automatic cycle operation (2 is
single cycle, 3 is repeat cycle). Accel /decel time of each step speed is determined
by E-029. When b-003 is not 0 and b-001=5, direction of multi-step speed operation
is determined by the value of E-018. Firstly confirm the corresponding binary value
according to direction
(
0
:
forward
;
1
:
reverse
)
of each step speed, as shown in
the follow figure. Then change to decimal system, namely E-018. When b-003 is not
0 and b-001 = 0, operation direction of each step speed is determined by states of SF,
SR terminals, and it is unrelated with E-018.