User Manual of SY5000 series AC Drive Keypad operation
~35~
Example of function setting and parameter regulation (under the status of direct
display)
E.g. 1
:
Set base frequency as 60Hz
:
No.
Operation
Explanation
1
Access to basic function status
,
display - - b - -
2
Access in parameter setting of basic function group,
display b-000
3
Keep pressing the key until display b-008
4
Display the current setting as 50.00
5
Keep pressing the key until display 60.00
6
Temporarily store current setting value 60.00 into
memory unit, the inverter will run according to new
setting value, and new data will be lost when power off.
Store current setting value 60.00 into memory unit, the
inverter will run according to new setting value, and new
data will be saved even if power off.
7
2~6
When need set other parameters of b group, please repeat
above 2~6 steps.
Press the key of FNC
,
and return to direct display mode
E.g. 2
:
Set the function of constant voltage control as 370V
:
No.
Operation
Explanation
1
Access in status of function group, display - - b - -
2
Press 1 time, display - - E - -