User Manual of SY5000 series AC Drive Parameter instrction
~46~
○
E-043
Resychronization
waiting time
0.0 ~ 100.0
0.1
s
20.0
Х
E-044
Slip
compensation
0.00 ~ 10.00
0.01
%
0.00
Х
E-045
Constant
voltage control
0 ~ 400
1
V
380
○
E-046
Free stop
command
0: decel stop
;
1: free stop is controlled by
PI1-COM status;
2: free stop is controlled by
PI2-COM status;
3: free stop is controlled by
PI3-COM status;
4: free stop is controlled by
PI4-COM status;
5: free stop.
1
0
○
E-047
Emergency stop
command
0: disabled;
1: enabled;
1
0
○
E-048
Alarm
allow when
emergency stop
0: Alarm output prohibited
when emergency stop, and
fault relay don’t act.
1: Alarm output allowed
when emergency stop and
fault relay acts.
1
0
○
E-049
Emergency stop
mode
0: free stop;
1: stop according to decel
time 1 ([b-018]);
2: stop according to decel
time 2 ([b-021]).
1
0
○
E-050
Tripping mode
when under
voltage
0: tripping
;
1: disabled
1
0
○
E-051
Fault trial
recovery project
command
0: disabled:
1: try recovery on
overcurrent (o.C) fault;
2: try recovery on
overvoltage (o.E) fault;
3: try recovery on IPM (F.Lt)
fault
;
4: reserved
;
5: try recovery on all above
faults.
1
0
○
E-052
Fault trial
recovery time
0.1 ~ 20.0
0.1
s
10.0