User Manual of SY5000 series AC Drive Commissioning
~89~
setting frequency.
⑤
In operation, enter the status of b-000, click
▲▼
keys, and can immediately
change motor rotation speed.
⑥
Click STOP key of control panel, the motor speed declines and then stop
rotating.
⑦
Set b-002 as 5, b-027 as 10.00Hz. Press RUN key and release, the inverter
runs to output frequency as 10.00Hz, and the motor rotates according to current
setting direction.
Observation of running status
①
Change frequency command or rotation direction, and observe whether there
is vibration and noise of the motor.
②
Please confirm the inverter whether works normally or not.
6.2.4 Load operation
After the motor works normally with no load, connect the load, and commission
with load.
Connect machanical load
①
After the motor stops, connect mechanical load.
②
Fastening screw, so that mechanical load fixed on the motor shaft.
Start inverter
①
Use control panel to start the inverter. It is the same as no load.
②
Change parameter value of b-035 from 0 to 1. And the motor reverse totates
until reaches the setting frequency.
③
In operation, enter the parameter setting status of b-000, click
▲▼
keys,
and can immediately change motor rotation speed.
④
Click STOP key of control panel, the motor speed declines and then stop
rotating.
⑤
Set parameter value of b-002 as 5, b-027 as 10.00Hz. Press RUN key and
release, the inverter runs to output frequency as 10.00Hz, and the motor rotates
according to current setting direction.
Observation of running status
①
Make sure that the running direction of mechanical load is whether correct
or not.
②
Change frequency command or rotation direction, and observe whether there
is vibration and noise of the motor.
③
When running, please switch to E-005 function code to see if the motor
current is excessive.