User Manual of SY5000 series AC Drive Parameter instrction
~37~
Chapter 5 Parameter instruction
5.1 Parameter table
Basic parameters (group b)
Modification mark in operation:
○
: The parameter can be set during operation;
Х
: The parameter can’t be set during operation
Function
code
Description
Setting range
Increment Unit Factory
setting
○
b-000
Frequency
setting
0.00 ~ [b-010]
0.01
Hz
0.00
○
b-001
Keypad
command
0: RUN/STOP keys disabled, RUN,
STOP and motional direction are
determined by status of SF, SR and
[b-036];
1 : R U N / S T O P o f t h e m o t o r
is controlled by status of PI1-
COM, motor motional direction is
determined by [b-035];
2 : R U N / S T O P o f t h e m o t o r
is controlled by status of PI2-
COM, motor motional direction is
determined by [b-035];
3 : R U N / S T O P o f t h e m o t o r
is controlled by status of PI3-
COM, motor motional direction is
determined by [b-035];
4: RUN/STOP of the motor is
controlled by status of PI4-COM,
the motor motional direction is
determined by [b-035];
5: RUN/STOP keys control RUN/
STOP of the motor, if [b-003]
=
0, motor motional direction is
determined by [b-035]; if [b-003]
≠
0, the direction is determined by
[E-018].
1
5