User Manual of SY5000 series AC Drive Parameter instrction
~58~
b-015 accel/decel time command
b-016 accel/decel mode1
0
:
linear mode
;
1
:
S-curve mode
b-017 accel time1
b-018 decel time1
b-019 accel/decel mode 2
0
:
linear mode
;
1
:
S-curve mode
b-020 accel time 2
b-021 decel time 2
b-015
Corresponding function
0
Select accel / decel time 1, accel /decel time and mode are determined by
b-016
,
b-017
,
b-018.
1~4
Select terminals of PI1
~
PI4. If selected terminal disconnects with COM,
select accel / decel time 1
,
accel / decel time and mode are determined by
b-016
,
b-017
,
b-018
;
If selected terminal connects with COM, select accel /decel time 2, accel
/decel time and mode are determined by b-019
,
b-020
,
b-021.
5
Select accel /decel time 2
,
accel/decel time and mode are determined by
parameters of b-019
,
b-020
,
b-021.