User Manual of SY5000 series AC Drive Parameter instrction
~50~
Code table of PID regulation (group P) (for SY5000-P series only)
○
P-014
PID sleep
control options
0: Sleep function disabled;
1: PI1 control sleep;
2: PI2 control sleep;
3: PI3 control sleep;
4: PI4 control sleep;
5: Sleep function enabled.
(Note: Sleep function disabled
if Pix does not short circuit with
COM; Sleep function enabled if
Pix short circuit with COM, x =
1,2,3,4)
1
0
○
P-015
PID sleep
delay
0.0~6000.0
0.1
s
60.0
○
P-016
PID sleep
frequency
0.00~[b-010]
0.01
Hz
0.00
○
P-017
PID sleep
wake-up value
0.00~100.00
0.01
%
0.00
○
P-018
PID sleep
wake-up delay
0.0~60.0
0.1
s
0.5
Code table of group G (for SY5000-P series)
Function
code
Description
Setting range
Increment Unit Factory
setting
Х
G-000 Option of ‘1 to
2 control’
0: ‘1 to 2 function’ disabled;
1: Y1, Y2 are selected as output
terminals of ‘1 to 2 control’
function;
2: Y1, Y3 are selected as output
terminals of ‘1 to 2 control’
function;
3: Y2, Y3 are selected as output
terminals of ‘1 to 2 control’
function.
(When [G-000]=1, settings
of [E-054], [G-010], [G-011]
disabled; when [G-000]=2, settings
of [E-054], [G-010], [G-012]
disabled; when [G-000]=3, settings
of [G-011], [G-012] disabled)
1
0
○
G-001
Automatic
switching
internal time
0 ~ 2000
1
min
0