User Manual of SY5000 series AC Drive Parameter instrction
~49~
○
P-004
Feedback
value channel
command
0: select analog voltage input V2-
GND
;
1: select analog current input I2-
GND
。
1
1
0
○
P-005 Feedback value
bias
-100.0 ~ 100.0
0.1
%
0.0
○
P-006 Feedback value
gain
0.0 ~ 10.0
0.1
1.0
○
P-007
Positive/
negative
characteristic
of feedback
value
0: positive characteristic;
1: negative characteristic
1
0
○
P-008
PID regulator
rate Kp
0.0 ~ 10.0
0.1
1.5
○
P-009
PID regulator
integration Ti
0.0 ~ 100.0
0.1
s
0.1
○
P-010
PID regulator
differential Td
0.0 ~ 100.0
0.1
s
0.0
○
P-011
Sample cycle
Ts
0.1 ~ 50.0
0.1
s
0.1
○
P-012
Bias limit
of PID
regulation
1 ~ 20
1
%
1
○
P-013
Display
magnification
of reference
value and
feedback
value
0.1 ~ 600.0(SY5000-G series)
0.1~100.0(SY5000-P series)
0.1
10.0