User Manual of SY5000 series AC Drive Parameter instrction
~51~
○
G-002
Adding-pump
delay time
0.0 ~ 6000.0
0.1
s
0.0
○
G-003
Subtracting-
pump delay
time
0.0 ~ 6000.0
0.1
s
0.0
○
G-004
Y1 closing
delay
0.0 ~ 6000.0
0.1
s
0.0
○
G-005
Y1
disconnecting
delay
0.0 ~ 6000.0
0.1
s
0.0
○
G-006
Y2 closing
delay
0.0 ~ 6000.0
0.1
s
0.0
○
G-007
Y2
disconnecting
delay
0.0 ~ 6000.0
0.1
s
0.0
○
G-008
Y3 closing
delay
0.0 ~ 6000.0
0.1
s
0.0
○
G-009
Y3
disconnecting
delay
0.0 ~ 6000.0
0.1
s
0.0
○
G-010
Water-supply
monitoring
function of
relay Y1
0: no output
(When [G-010]=0, output of Y1 is
determined by [E-054] );
1: frequency upper limit monitoring;
2: frequency lower limit monitoring
3: feedback value upper limit
monitoring;
4: feedback value lower limit
monitoring
1
0
○
G-011
Water-supply
monitoring
function of
relay Y2
1
0
○
G-012
Water-supply
monitoring
function of
relay Y3
1
0
○
G-013
Upper limit
frequency of
monitoring
signal
[G-014]~b010
0.01
Hz 50.00
○
G-014
Lower limit
frequency of
monitoring
signal
0.00~[G-013]
0.01
Hz
0.00