User Manual of SY5000 series AC Drive Parameter instrction
~47~
○
E-053
Fault trial
recovery times
0~8 (times)/9: always try
recovery faults
1
1
Х
E-054
Open collector
output
command
(for SY5000-G
series only)
0: operation signal—— if
output frequency is higher than
[E-055], then open collector
between OUT-COM output low
level;
1: frequency arrival signal——
if output frequency is in the
range of (setting frequency ±
[E-056]) , then open collector
between OUT and COM output
low level;
2: overload alarm signal——
if overload fault happens,then
open collector between OUT
and COM output low level.
1
0
Х
E-054
Output
selection of
relay Y1
(for SY5000-P
series only)
0: operation signal—— when
output frequency is higher than
[E-055] settings, relay closes,
otherwise disconnects;
1: frequency arrival signal
—— when output frequency
is in the range of ± [E-056]
settings, relay closes, otherwise
disconnects;
2: overload alarm signal——
when overload failure happens,
relay closes, otherwise
disconnects;
3: operation signal in zero
speed—— when output
frequency is 0 and still in
operation status, relay closes,
otherwise disconnects;
4: under-voltage locking
signal—— When under-
voltage failure happens
(display “P.Off”), relay closes,
otherwise disconnects.
(Note: relay closing means
Y10-Y11 connecting and
Y10-Y12 disconnecting; relay
disconnection means Y10-Y11
disconnecting, and Y10-Y12
closing).
1
0