Chapter 3
Maintaining the Netra X4200 M2 Server
43
■
“Reconnecting Cables to the Server” on page 130
■
“Powering On the Server” on page 131
Replacing a Hard Drive
The hard disk drives in the server are hot-pluggable, but this capability depends on
how the hard drives are configured. To hot-plug a drive you must take the drive
offline (prevent any applications from accessing it, and remove the logical software
links to it) before you can safely remove it.
The following situations inhibit the ability to perform hot-plugging of a drive:
■
The hard drive provides the operating system, and the operating system is not
mirrored on another drive.
■
The hard drive cannot be logically isolated from the online operations of the
server.
If your drive falls into the conditions listed above, you must shut down the system
before you replace the hard drive. See
“Powering Off the Server” on page 28
.
Note –
Replacing a hard drive does not require removing the server from a rack.
Nor does the procedure require removing the top cover of the server.
Removing a Hard Drive
1. Press the green tabs on either side of the bezel and pull the bezel forward and
down (
FIGURE 3-16
).
FIGURE 3-16
Opening the Bezel
Summary of Contents for Netra X4200 M2
Page 10: ...x Netra X4200 M2 Server Service Manual May 2007...
Page 14: ...xiv Netra X4200 M2 Server Service Manual May 2007...
Page 24: ...10 Netra X4200 M2 Server Service Manual May 2007...
Page 46: ...32 Netra X4200 M2 Server Service Manual May 2007 Sun ESD mat part number 250 1088...
Page 133: ...Chapter 3 Maintaining the Netra X4200 M2 Server 119...
Page 134: ...120 Netra X4200 M2 Server Service Manual May 2007...
Page 146: ...130 Netra X4200 M2 Server Service Manual May 2007...
Page 154: ...138 Netra X4200 M2 Server Service Manual May 2007...
Page 172: ...156 Netra X4200 M2 Server Service Manual May 2007...