Chapter 3
Maintaining the Netra X4200 M2 Server
97
FIGURE 3-71
Removing a Power Supply From the Chassis
5. Continue to
“Installing a Power Supply” on page 97
.
Installing a Power Supply
1. Remove the replacement power supply from its packaging and place the
supply on an antistatic mat.
2. Align the replacement power supply with the empty power supply bay.
3. Slide the power supply into bay until it is fully seated (
FIGURE 3-72
).