15 | Technical data
90 / 100
Installation instructions sonnenBatterie 10
Rated short-withstand current
10 kA
Separation principle
no galvanic isolation, transformer-less
Fulfilled standards and directives
AS/NZS 4777.2; CEI 0-21; EMC Directive 2014/30/EU;
EN 50438; G98/99; IEC 61000-6-1; IEC 61000-6-3; IEC
62040-1; IEC 62109-1; IEC 62619; Low Voltage Directive
2014/35/EU; UN 38.3; VDE-AR-N 2510-2; VDE-AR-
N 2510-50; VDE-AR-N 4105
Power measurement
Voltage measurement inputs
Nominal voltage (AC): 230 V (L-N), 400 V (L-L) | max.
connectible conductor cross-section: 1.5 mm²
Clamp-on current transformer
Max. measurable current: 60 A (standard), optional up to
400 A
Dimensions/weight
13
sonnenBatterie
10/5,5
10/11
10/16,5
10/22
10/27,5
Dimensions (H/W/D) in cm
172-184/69/27
2 x 172-184/69/27
Height without feet in cm
161
Total weight in kg
115
172
268
325
382
Ambient conditions
Environment
Indoor (conditional)
Operating temperature range
14
-5 °C ... 45 °C
Storage temperature range
0 °C ... 40 °C
Transport temperature range
-15 °C ... 50 °C
Max. rel. humidity
85%, non-condensing
Permissible installation altitude
2,000 m above sea level
Pollution degree
2
Additional ambient conditions
• No direct sunlight.
• No danger due to flooding.
• No corrosive and explosive gases. The maximum permissible ammonia content is
20 ppm.
• No dust, especially flour dust or sawdust.
• No vibrations.
• Installation room should be ventilated.
• Free space available.
• Floor is suitable for heavy loads.
• Observe all fire control standards.
• Observe applicable local building codes.
13
From 16.5 kWh: storage system with extension
14
Optimal: 5 °C … 30 °C | Derating possible below 5 °C / above 30 °C.
Summary of Contents for sonnenBatterie 10
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ...sonnen GmbH Am Riedbach 1 D 87499 Wildpoldsried ...