9 | sonnenProtect 4000 (optional)
70 / 100
Installation instructions sonnenBatterie 10
9.6.2 Positioning components in the electrical distributor
The following components must be installed in the electrical distributor for the
sonnenProtect:
•
Miniature circuit breaker (MCB) | type B | 20 A
A miniature circuit breaker with type B tripping characteristics and a nominal current of
20 A must be installed in the mains line
at the input line
(Mains line for sonnenProtect, see
Overview – sonnenProtect lines [P. 67]) of the sonnenProtect.
•
Residual current device (RCD)
at the output
of the sonnenProtect. This
RCD protects against electric shock in the backup circuit. A
that meets the relevant country-specific regulations and is suitable for local grid conditions
must be used.
9.6.3 Wiring the sonnenProtect
Condition:
ü
Connect the sonnenProtect and the other components in the electrical distributor as
shown in the following figure.
• Figure 'Circuit diagram overview – electrical connection in single-phase mains [P. 71]’
shows the installation of a sonnenBatterie 10 with a sonnenProtect 4000 in single-phase
mains.
• The area marked in grey shows the system extension where the sonnenProtect was ad-
ded.