8 | Using digital inputs/outputs (optional)
58 / 100
Installation instructions sonnenBatterie 10
Level
Max. active power
1
Feed-in limit of PV system in %
plus
10%
2
Feed-in limit of PV system in %
minus
15%
3
0%
The values for levels 1 and 2 depend on the
individual
feed-in limit of the PV system in
question. The addition or subtraction of the stated percent values leads to an optimal regu-
lation by the storage system.
Example:
The feed-in of the PV system is limited to 50% of the rated power. The following values
need to be entered in the commissioning assistant.
Level 1
60%
(50% plus 10%)
Level 2
35%
(50% minus 15%)
Level 3
0%