Connecting the storage system | 6
KD-557 | 1000241 | EN | 02
31 / 100
6 Connecting the storage system
DANGER
Electrical work on the storage system and electrical distributor
Danger to life due to electrocution!
Switch off the storage system to electrically isolate it.
Disconnect the relevant electrical circuits.
Secure against anyone switching on the device again.
Wait five minutes so the capacitors can discharge.
Check that the device is disconnected from the power supply.
Only licensed electricians are permitted to carry out electrical work.
DANGER
Touch voltage in the event of a fault
Danger to life due to electrocution!
Install a selective residual current device with a nominal differential current
of 300 mA in TT networks. Nominal differential currents of 100 mA or
30 mA are also possible. The type of RCD must be selected depending upon
the local conditions of the network.
NOTICE
Danger due to touching live components on the power module
Damage to components of the power module due to electrostatic discharge
(
Do not remove the touch guard on the power module and do not open the
power module.
Do not touch any components under the touch guard on the power module.
Do not touch any components of the inverter by opening the power mod-
ule.