Technical data | 15
KD-557 | 1000241 | EN | 02
89 / 100
15 Technical data
15.1 sonnenBatterie 10
System data (AC)
General
sonnenBatterie
10
Nominal voltage
230/240 V
Nominal frequency
50 Hz
Nominal power
10
4,600/4,800 W
Nominal current
20 A
Power factor range
0.9 capacitive ... 0.9 inductive
Network Impedance (Z
max
)
0.34 Ω
Flicker P
st
(Z
ref
)
0.221 Ω
Flicker P
lt
(Z
ref
)
0.219 Ω
Current (Max. continous)
20 A
Max. output fault current
120 mA
Inrush current
0 A
Mains connection
single-phase, L / N / PE
Max. ext. overcurrent protection
25 A, 1ph
Mains topology
TN / TT
Mains connection fuse
Miniature circuit breaker | Type B | 20 - 25 A
Depends on capacity
11
sonnenBatterie
10/5,5
10/11
10/16,5
10/22
10/27,5
Nominal capacity
5.5 kWh
11 kWh
16.5 kWh
22 kWh
27.5 kWh
Usable capacity
5 kWh
10 kWh
15 kWh
20 kWh
25 kWh
Charging/discharging power
12
3.4 kW
4.6/4.8 kW
4.6/4.8 kW 4.6/4.8 kW
4.6/4.8 kW
Charging/discharging current
14.8/14.2 A
20 A
20 A
20 A
20 A
Battery data (DC)
Cell technology
lithium iron phosphate (LiFePO4)
Nominal voltage
102.4 V
Working voltage
204.8 V
Current (Max. continous)
40 A
Short-circuit current
50 A
Min. number of battery modules
2
Max. number of battery modules
10
Safety
Protection class
I / PE conductor
Required fault current monitoring
In TT networks: Residual current device (RCD) with a rated
differential current of 300 mA; requirements on site must
be observed.
Degree of Protection
IP30
Overvoltage category
2
10
at cos phi = 1
11
from 16.5 kWh: storage system with extension
12
at cos phi = 1
Summary of Contents for sonnenBatterie 10
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ...sonnen GmbH Am Riedbach 1 D 87499 Wildpoldsried ...