sonnenProtect 4000 (optional) | 9
KD-557 | 1000241 | EN | 02
73 / 100
Connecting the signal line and AC cable
Connect the signal line to the central unit of the storage system (
Protect
) using the
pre-assembled plug.
Connect the AC cable to the central unit (
AC Protect
) using the pre-assembled plug.
9.6.4 Attaching safety label to the distributor
DANGER
Electrical installation remains live in event of grid outage
Danger to life due to electrocution!
To warn electricians:
Attach the safety label shown below (included in scope of delivery) to the
relevant electrical distributor.
Illustration 31: Label for attachment to the electrical distributor
9.6.5 Attaching type label to storage system
As the sonnenProtect 4000 constitutes an add-on to the storage system, a
duplicate of the type label for the sonnenProtect must be affixed to the stor-
age system.
Affix the type plate for the sonnenProtect 4000, which is included in the scope of de-
livery, to the cover of the storage system above the inspection window.