Installing the storage system | 5
KD-557 | 1000241 | EN | 02
25 / 100
2.
5.
3.
1.
4.
Install the levelling elements on the feet.
Use two of the four slotted holes each to define the height of the storage system.
Install the two feet using the screws, contact discs and nuts from the installation equip-
ment pack.
CAUTION! Two contact discs must be installed for each screw, as shown in
the figure.
Tighten the screws with a torque of
8 Nm
.
5.2.4 Drilling the holes
Lean the mounting frame with the installed feet on the wall at the installation location.
When installing the storage system without feet:
Place the mounting frame on a suit-
able object so that the required 10 cm distance from the floor can be achieved. Altern-
atively, you can install the feet on the mounting frame in order to mark out the holes,
and then remove the feet again.
Mark out the eight holes for the wall bracket. When the optional
crossbars
are moun-
ted, the outer
or
the inner openings can be used for wall mounting.
Drill the holes with a suitable diameter for the selected mounting material.
Insert suitable wall plugs in the holes.
5.2.5 Securing the mounting frame to the wall
Ensure that the mounting frame is flat against the wall.
5.2.6 Straightening and levelling the mounting frame
• Use the slotted holes and screws (four per side) on the outer edges of the mounting
frame to straighten it.