animeo IB+
4 Zone/8 Zone TouchBuco BACnet
2020/04/30
Seite 47
Object name
Object-Type
Object-
ID
COV Unit
Description
SNOW_FROST_ICE_RAIN_BV BINARY VALUE
BV604
Shows if snow, frost, ice or rain is active
due to exceeded on delay time, precipita-
tion and temperature
LOCK_TIMER_BV
BINARY VALUE
BV605
Shows that local control is locked for a
pre-defined period
MANUAL_BV
BINARY VALUE
BV606
Shows that a manual command is exe-
cuted
TIMER_BV
BINARY VALUE
BV607
Shows that an order is sent for a pre-de-
fined time or period
BLOCK_HEAT_BV
BINARY VALUE
BV608
Shows that the blinds are closed to avoid
the room from overheating
SOLAR_HEATING_BV
BINARY VALUE
BV609
Shows that the blinds are opened to take
advantage of the sun
MAINTAIN_HEAT_BV
BINARY VALUE
BV610
Shows that the blinds are closed to pre-
vent the room from cooling out
COOLING_BV
BINARY VALUE
BV611
Shows that the windows are opened to
take advantage of the lower outside tem-
perature
SUN_PROTECTION_BV
BINARY VALUE
BV612
Shows that the blinds are closed due to
glare protection
UP_BV
BINARY VALUE
BV613
Write "1" to send group to upper end limit
STOP_BV
BINARY VALUE
BV614
Write "1" to stop group
DOWN_BV
BINARY VALUE
BV615
Write "1" to send group to lower end limit
MY_POSITION_BV
BINARY VALUE
BV616
Recalls the pre-defined position/angle
LOCK_UNLOCK_BV
BINARY VALUE
BV617
Write "1" to lock the local control
BLIND_POSITION_AV
ANALOG VALUE AV600
98 Percent
Write a value between 0 % and 100 % to
move the blinds to the desired position
BLIND_ANGLE_
ANALOG VALUE AV601
90 Degree angular
Write a value between 0° and 90° or -90°
and 90° to move the blinds to the desired
angle
ALARM_BV
BINARY VALUE
BV600
Shows status of external alarm input
LOCK_BV
BINARY VALUE
BV701
Shows that local control is locked. Control
via TouchBuco is still possible.
ERROR_BV
BINARY VALUE
BV702
Shows critical defect of wind sensor, wind
direction sensor and Outside Sensor Box
WIND_BV
BINARY VALUE
BV703
Shows that wind function is active due to
exceeded wind threshold and on delay
time
SNOW_FROST_ICE_RAIN_BV BINARY VALUE
BV704
Shows if snow, frost, ice or rain is active
due to exceeded on delay time, precipita-
tion and temperature
LOCK_TIMER_BV
BINARY VALUE
BV705
Shows that local control is locked for a
pre-defined period
MANUAL_BV
BINARY VALUE
BV706
Shows that a manual command is exe-
cuted
TIMER_BV
BINARY VALUE
BV707
Shows that an order is sent for a pre-de-
fined time or period
BLOCK_HEAT_BV
BINARY VALUE
BV708
Shows that the blinds are closed to avoid
the room from overheating
SOLAR_HEATING_BV
BINARY VALUE
BV709
Shows that the blinds are opened to take
advantage of the sun
MAINTAIN_HEAT_BV
BINARY VALUE
BV710
Shows that the blinds are closed to pre-
vent the room from cooling out
COOLING_BV
BINARY VALUE
BV711
Shows that the windows are opened to
take advantage of the lower outside tem-
perature
SUN_PROTECTION_BV
BINARY VALUE
BV712
Shows that the blinds are closed due to
glare protection
UP_BV
BINARY VALUE
BV713
Write "1" to send group to upper end limit
Summary of Contents for animeo IB+ 4 Zone Touch Building Controller