Object name
Object-Type
Object-
ID
COV Unit
Description
WIND_SPEED_1_AI
ANALOG INPUT
AI0
1
74 Meters-per-second Shows current wind speed value
WIND_SPEED_2_AI
ANALOG INPUT
AI1
1
74 Meters-per-second
WIND_DIRECTION_AI
ANALOG INPUT
AI2
5
90 Degrees Angular
Shows current wind direction value
SUN_1_AI
ANALOG INPUT
AI3
1000 37 Luxes
Shows current brightness value
SUN_2_AI
ANALOG INPUT
AI4
1000 37 Luxes
SUN_3_AI
ANALOG INPUT
AI5
1000 37 Luxes
SUN_4_AI
ANALOG INPUT
AI6
1000 37 Luxes
SUN_5_AI
ANALOG INPUT
AI7
1000 37 Luxes
SUN_6_AI
ANALOG INPUT
AI8
1000 37 Luxes
SUN_7_AI
ANALOG INPUT
AI9
1000 37 Luxes
SUN_8_AI
ANALOG INPUT
AI10
1000 37 Luxes
OUTSIDE_TEMPERATURE_AI ANALOG INPUT
AI11
1
62 Degrees-Celsius
Shows current outside temperature value
PRECIPITATION_BI
BINARY INPUT
BI0
1
Shows current precipitation value
1= precipitation; 0= no precipitation
INSIDE_TEMPERATURE_AI
ANALOG INPUT
AI12
1
62 Degrees
Shows current inside temperature value
INSIDE_TEMPERATURE_AI
ANALOG INPUT
AI13
1
62 Degrees
INSIDE_TEMPERATURE_AI
ANALOG INPUT
AI14
1
62 Degrees
INSIDE_TEMPERATURE_AI
ANALOG INPUT
AI15
1
62 Degrees
ALARM_BV
BINARY VALUE
BV100
Shows status of external alarm input
LOCK_BV
BINARY VALUE
BV101
Shows that local control is locked. Control
via TouchBuco is still possible.
ERROR_BV
BINARY VALUE
BV102
Shows critical defect of wind sensor, wind
direction sensor and Outside Sensor Box
WIND_BV
BINARY VALUE
BV103
Shows that wind function is active due to
exceeded wind threshold and on delay
time
SNOW_FROST_ICE_RAIN_BV BINARY VALUE
BV104
Shows if snow, frost, ice or rain is active
due to exceeded on delay time, precipita-
tion and temperature
LOCK_TIMER_BV
BINARY VALUE
BV105
Shows that local control is locked for a
pre-defined period
MANUAL_BV
BINARY VALUE
BV106
Shows that a manual command is exe-
cuted
TIMER_BV
BINARY VALUE
BV107
Shows that an order is sent for a pre-de-
fined time or period
BLOCK_HEAT_BV
BINARY VALUE
BV108
Shows that the blinds are closed to avoid
the room from overheating
SOLAR_HEATING_BV
BINARY VALUE
BV109
Shows that the blinds are opened to take
advantage of the sun
MAINTAIN_HEAT_BV
BINARY VALUE
BV110
Shows that the blinds are closed to pre-
vent the room from cooling out
COOLING_BV
BINARY VALUE
BV111
Shows that the windows are opened to
take advantage of the lower outside tem-
perature
SUN_PROTECTION_BV
BINARY VALUE
BV112
Shows that the blinds are closed due to
glare protection
UP_BV
BINARY VALUE
BV113
Write "1" to send group to upper end limit
STOP_BV
BINARY VALUE
BV114
Write "1" to stop group