6 Settings
Alarm, Rain/Snow, Frost/Ice, Wind and Lock Timer are safety functions. When enabling individual safety
functions, the animeo IB+ or Smoove UNO IB+ Motor Controllers are locked for further operator commands
(local operation via buttons, radio functions, etc.) and low-priority automatic commands. The "IB" LED on the
motor controller lights up red to indicate that commands have been locked.
6.1 Security
6.1.1 Alarm
An alarm can be triggered via the separate floating input. The alarm function has top priority and, in the
event of an alarm signal, further operator commands (local operation via buttons, radio functions, etc.), as
well as all automatic commands are locked. The behavior of the end products/motorized products in a zone
is defined in the event of an alarm and when the alarm is terminated. The "IB" LED on the motor controller
lights up red to indicate that commands have been locked.
You can navigate through the setting using the grey "forward" and "backward" arrows.
To enable the alarm function you need to move the slider to the right.
Settings:
ALARM ON
Position of the end product/motorized product in the event of an alarm signal
Lock Only: The end products/motorized products in a zone stop moving and low-priority manual and auto-
matic commands are locked.
Up Priority: The end products/motorized products in a zone move to the upper end limit and low-priority man-
ual and automatic commands are locked.
Down Priority: The end products/motorized products in a zone move to the lower end limit and low-priority
manual and automatic commands are locked.
ALARM OFF
Position of the end product/motorized product once an alarm signal has been termi-
nated
H
This function requires the running times and angles to have been programmed for the end products/
motorized products.
No Action: A travel command is not issued until the status of a different function is changed (e.g. sun).
Standard: The end products/motorized products move to the standard position. The standard position only
needs to be defined once under "Options/System Settings".
Position: The end products/motorized products are moved to an adjustable position here (%) or, in the case
of Venetian blinds, set to an adjustable angle (°).
My Position: The end products/motorized products are moved to the intermediate position programmed in