animeo IB+
4 Zone/8 Zone TouchBuco BACnet
2020/04/30
Seite 10
Interior Plisseé:
Made of textile material and behaves like a roller shutter, i.e. just moving up and down.
Interior Venetian blind 90°/- 90°:
This is a blind-based system that moves vertically and can be turned.
Interior curtain:
With electric drive for opening and closing interior curtains and shades.
Window opened inwards:
With electric drive for opening and closing inwards. When setting the other
parameters, please note that 0 % corresponds to the closed position and 100 % to the opened position. In
the “Standard position” menu (s. chapter 6.5.1.4), this default setting can nevertheless be inverted.
1.13 Set Run Time
The runtime is the time required by an end product/motorized product (roller shutters, Venetian blinds, etc.)
to move from its uppermost position (0 %) to its lowermost position (100 %) and vice versa. With windows,
the runtime is from fully open (100 %) to fully closed (0 %). The runtime is important to ensure that an end
product/motorized product can also be moved to an intermediate position (defined in percent from 0 % to
100 %).
H
In the case of large/long motorized products, the runtime during downward travel can deviate from the
runtime for upward travel by several seconds (total distance covered by motorized product moving up and
down).
When using end products/motorized products with turning (e.g. Venetian blinds): If a position and an angle
are to be approached, the runtime must be entered very accurately, as the rotation for the angle only starts
once the runtime entered has elapsed.
If there are motorized products of varying lengths within a given zone, you must enter the longest time first.
You can make precision adjustments for the shorter motorized products in this zone later under "Settings".
When exiting the screen, these settings are automatically sent to the motor controllers of the corresponding
zone.
1.14 Set Tilt Time
The angle is the time required by a Venetian blind to turn the slats from fully closed to fully open. This time is
typically in the range from 0.8 to 2 seconds.
The right angle needs to be determined. Three test commands are available for this: 90°, 45° and 0°.
Interior
Exterior
Test the commands one after the other. If necessary, alter the angle until optimum results are achieved for
the three angles. Recommended: Start at 1.5 seconds and adjust the value in 0.1 second steps. For exam-
ple, if 45° is more like 30° during testing, reduce it by 0.1 seconds. If 45° is more like 70° during testing,
increase it by 0.1 seconds.
When exiting the screen, these parameters are automatically sent to the motor controllers of the correspond-