animeo IB+
4 Zone/8 Zone TouchBuco BACnet
2020/04/30
Seite 37
6.5.2.2 Learn Zones
After you have checked the wiring of the motor controllers and set up the zones correctly, you can now as-
sign the motor controllers/drives to the zones. You can choose between standard assignment and advanced
assignment here.
PROCEDURE 1:
Set the order manually
Enable programming mode by pressing "START". All LEDs on the motor controller now flash in circulation to
indicate that the unit is ready for programming mode. With the Smoove UNO IB+, the LED flashes in various
colors. To assign the corresponding motorized product to the selected zone, press the connected button or
the programmed remote control on the motor controller. Local operator functionality is integrated with the
Smoove UNO IB+. On the animeo IB+ motor controller, however, it needs to be connected. With the 4-unit
animeo IB+ Motor Controller with pluggable radio receiver, you can even use the remote control. All drives
that move as a result of local operator actions are now automatically assigned to the corresponding zone. As
soon as all motor controllers have been programmed, you need to complete the procedure by clicking on OK
in the "End of programming finished" field.
H
The programming mode is enabled for a maximum of 10 minutes. Once this time has elapsed, the motor
controllers automatically exit this mode. If the time was not enough to make all necessary settings, you
can re-enable programming mode. If a motor controller was already assigned to a zone, the previous
value will be overwritten with the new programming process.
The "
Learn not assigned Motor Controllers
" option: Motor controllers that have already been programmed
are excluded from assignment here. This prevents existing assignments from being overwritten by mistake.
You can tell when a motor controller is in programming mode, as the unit's LEDs run a circulating pattern.
With the Smoove UNO IB+, the LED flashes in various colors. Tap the box to activate this option.
The right arrow button grants you access to the next "PROCEDURE 2:" settings level.
PROCEDURE 2:
Individual motor controllers are assigned via device number (ID). As such, you require the ID address of the
motor controllers. These can be found on barcode stickers on the devices themselves (example
"ID:8390363"). With the Smoove UNO IB+, the address is printed on the rear of the front panel.
Set a check mark for the outputs of the motor controller which are to be assigned to the zone (1 – 4 or 1 - 8).
Enter the ID address of the motor controller in the field and then hit "Learn". Conversely, you can also delete
individual motor controller assignments by clicking on "Unlearn" instead of "Learn".
The right arrow button grants you access to the next settings level.
Learn error zone:
Here, an output converter can be assigned to the error zone for the purposes of error output to external
controls. The function is identical to procedure 1: Set the order manually.
The up contact is closed when the system is locked by a safety-related error.
The down contact is closed when a sensor error occurs, but the system still works.
Learn error zone ID:
Enter the ID address of the output converter in the field and then hit "Learn". Conversely, you can also delete
individual output converter assignments by clicking on "Unlearn" instead of "Learn".
Summary of Contents for animeo IB+ 4 Zone Touch Building Controller