Setting the wind and wind direction:
Selecting the wind sensors: When setting up the sensor system, you either selected the Compact Sensor
(just one wind sensor) or the Outside Sensor Box (up to two wind sensors). You now need to select which
wind sensor is to be used as reference for this zone. If two sensors are selected, the highest value of the two
is always used.
Threshold for wind and wind direction:
Adjustment range from 2 m/s to 30 m/s.
Delay time wind and wind direction:
Adjustment range "On" from 0 to 60 seconds. Adjustment range "Off"
from 0 to 255 minutes.
Wind On:
Setting the behavior of the motorized product in the event of a wind alarm
Lock Only
The end products/motorized products in a zone stop moving and low-priority manual and auto-
matic commands are locked.
Up Priority
The end products/motorized products in a zone move to the upper end limit and low-priority
manual and automatic commands are locked.
Down Priority
The end products/motorized products in a zone move to the lower end limit and low-priority
manual and automatic commands are locked.
Wind Direction Area:
Specify the start and end of the range. The adjustment range is from 0° to 360°,
whereby 0° corresponds to due north.
6.1.5 Lock Timer
The "Lock Timer" function is used to move the end products/motorized products of an area to a position at a
certain time (adjustable), where they remain until enabled. By that time, further operator commands (local
operation via buttons, radio control, etc.) and low-priority automatic commands are locked. The "IB" LED on
the motor controller lights up red to indicate that commands have been locked.
Up to 6 switching commands can be set per week day (Monday to Sunday). Each switching command can
be freely defined. "Not Used" is displayed as standard, i.e. not set and not enabled. To save time, settings
from one day can be copied to another.
Enabling the function:
The function is enabled when you move the slider to the right.
Setting a switching command with disabling function:
First select a day and then one of the six potential switching commands by clicking on the yellow icon. The
setting procedure always remains the same. To return to the main menu, simply press the arrow at the
bottom right.
Switching command options:
Not Used:
The command has not been set or enabled.
On Time:
The disabling function is active from this time onwards. The timing can either be a fixed time of the
day or be based on the dusk and dawn times (please see “Switching commands at dusk” for an explanation
on this). The behavior of the motorized product is defined after setting the timing:
Lock Only:
The end products/motorized products in a zone stop moving and low-priority manual and auto-
matic commands are locked.
Up Priority
The end products/motorized products in a zone move to the upper end limit and low-priority
manual and automatic commands are locked.