12. OPTIONS AND AUXILIARY EQUIPMENT
(4) Connection of the regenerative option
POINT
For the sizes of wires used for wiring, refer to section 12.6.
The regenerative option will cause a temperature rise of 100 relative to the ambient temperature. Fully
examine heat dissipation, installation position, used cables, etc. before installing the option. For wiring, use
flame-resistant wire and keep them clear of the regenerative option body. Always use twisted cables of max.
5m length for connection with the driver.
(a) LECSB
□
-
□
Always remove the wiring from across P-D and fit the regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is disconnected when the regenerative option
overheats abnormally.
D
P
C
G4
G3
C
P
Regenerative option
5m or less
Servo amplifier
Always remove the lead from across P-D.
(Note 2)
Cooling fan
(Note 1)
Note 1. Make up a sequence which will switch off the magnetic contactor when abnormal
heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
Driver
(Note 1)