5. PARAMETERS
5.3.3 Analog monitor
The servo status can be output to two channels in terms of voltage.
(1) Setting
Change the following digits of parameter No.PC14, PC15.
Analog monitor (MO1) output selection
(Signal output to across MO1-LG)
Parameter No.PC14
0 0 0
Parameter No.PC15
Analog monitor (MO2) output selection
(Signal output to across MO2-LG)
0 0 0
Parameters No.PC39 and PC40 can be used to set the offset voltages to the analog output voltages. The
setting range is between 999 and 999mV.
Parameter No.
Description
Setting range [mV]
PC39
Used to set the offset voltage for the analog monitor 1 (MO1).
999 to 999
PC40
Used to set the offset voltage for the analog monitor 2 (MO2).