Functions
8.4 Configuration
ULTRAMAT 23
Manual, 3/2016, A5E37100388-003
139
Table 8- 4
Overview of relay assignments
Function
Relay de-energized
Relay energized
Signaling
Limit
Limit has been triggered
Limit
(see section Parameters: Limits
(Page 128))
Measuring range
Range 2
Range 1
-
Status messages
Fault
Fault present
Maintenance request
Maintenance
request
CAL/MEAS
Measure
AUTOCAL
AUTOCAL
Function control
Function control
present
During warm-up phase (approx. 30
min), AUTOCAL,
uncoded
External solenoid valves
Zero gas
Zero gas flowing
Ext. solenoid valve open
Calibration gas (sample
gas inlet)
Calibration gas flowing
Ext. solenoid valve open
Sync.
Synchronization signal is
output
AUTOCAL only "Zero gas flow" and
adjustment not during sample gas
purging phase
The pin assignments of the relays in the de-energized state are described in section Pin
assignments (Page 54).
The functions which can be assigned to the relays have the following meanings:
Limit messages
The upper and lower limits can be defined as events for trig-
gering relays. Select the desired relay(s) in the second and
third lines of this menu.
This function is specific to the component.
Relays for MR
A relay for range switchover can be assigned to each compo-
nent. This guarantees reliable assignment of the analog output
signal to the currently active range, especially with autoranging
(see section Parameter: Measuring ranges (Page 125)).
Summary of Contents for ULTRAMAT 23
Page 2: ......
Page 10: ...Table of contents ULTRAMAT 23 10 Manual 3 2016 A5E37100388 003 Index 239 ...
Page 66: ...installation ULTRAMAT 23 66 Manual 3 2016 A5E37100388 003 ...
Page 147: ...Functions 8 4 Configuration ULTRAMAT 23 Manual 3 2016 A5E37100388 003 147 ...
Page 160: ...Functions 8 5 Automatically executed functions ULTRAMAT 23 160 Manual 3 2016 A5E37100388 003 ...
Page 194: ...Spare parts accessories 13 5 IR analyzer units ULTRAMAT 23 194 Manual 3 2016 A5E37100388 003 ...
Page 195: ...Spare parts accessories 13 5 IR analyzer units ULTRAMAT 23 Manual 3 2016 A5E37100388 003 195 ...
Page 196: ...Spare parts accessories 13 5 IR analyzer units ULTRAMAT 23 196 Manual 3 2016 A5E37100388 003 ...
Page 229: ...Appendix A 4 Returned delivery ULTRAMAT 23 Manual 3 2016 A5E37100388 003 229 ...
Page 230: ...Appendix ULTRAMAT 23 230 Manual 3 2016 A5E37100388 003 ...
Page 238: ...List of abbreviations C 1 List of abbreviations ULTRAMAT 23 238 Manual 3 2016 A5E37100388 003 ...