System overview
1.9 Connection
SIRIUS Innovations
78
System Manual, 01/2011, A8E56203870002-03
Insulating stop
With conductor cross-sections which are ≤ 1 mm
2
, you should use an insulating stop to
prevent the conductor insulation from being clamped. The insulating stop can be used with
the following devices:
Table 1- 25 Overview table - Use of insulating stop for conductor cross-sections ≤ 1 mm
2
Size S00
Size S0
Main circuit
Control circuit
Main circuit
Control circuit
3RT2/3RH2 contactors (basic
devices)
2
2
—
1
Accessories for 3RT2 contactors
(e.g. auxiliary switches)
—
1
—
1
3RF34 solid-state switching
devices
—
—
2
—
3RW30/40 soft starters
2
0
—
0
3RV2 motor starter protectors
(basic devices)
2
1
—
1
Accessories for 3RV2 motor
starter protectors (e.g. auxiliary
switches)
—
1
—
1
3RU2 thermal overload relays
—
1
—
1
3RB3 solid-state overload relays
—
0
—
0
3RA6 compact starters
—
—
—
0
3RA27/3RA28 function modules
—
0
—
0
3RR2 current monitoring relays
—
0
—
0
0: No insulating stop required
1: Insulating stop 3RT1916-4AJ02
2: Insulating stop 3RT2916-4AJ02
—: Not relevant (e.g. conductor cross-section ≤ 1 mm
2
) or not available
The graphic below shows how the insulating stop is used:
Figure 1-35 Insulating stop on spring-loaded connection system