![Siemens SIRIUS 3RH Series System Manual Download Page 351](http://html.mh-extra.com/html/siemens/sirius-3rh-series/sirius-3rh-series_system-manual_383139351.webp)
SIRIUS 3RF34 solid-state switching devices
3.11 Technical data
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
351
General data
Permissible mounting position
r
r
r
r
Insulation strength at 50/60 Hz
(main/control circuit to floor)
V rms 4000
1)
These products are Class A products. Their use in residential areas can cause radio frequency interference. In this
case, the user can be held liable for taking additional measures to attenuate such interference.
2)
Running star-connected three-phase motors (particularly < 1 kW) with electromechanical contactors can cause
significant electromagnetic interference. Such interference can cause solid-state reversing contactors being used in the
vicinity to malfunction. Provision should be made for appropriate EMC surge suppressors on the sources of interference.
Suitable surge suppressors are described in Chapter 3 of Catalog LV1.
3)
For solid-state reversing contactors, the following applies: To maintain the values a 3TX7 462-3L surge suppressor (see
Catalog LV1) should be used between phases L1 and L3, as close as possible to the reversing contactor.
Reference
More information ...
Can be found in the chapter titled ...
About the environments in which solid-state
switching devices are used
Summary of Contents for SIRIUS 3RH Series
Page 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Page 2: ......
Page 785: ......