![Siemens SIRIUS 3RH Series System Manual Download Page 244](http://html.mh-extra.com/html/siemens/sirius-3rh-series/sirius-3rh-series_system-manual_383139244.webp)
SIRIUS 3RT2 contactors/contactor assemblies
2.8 Technical data
SIRIUS Innovations
244
System Manual, 01/2011, A8E56203870002-03
Type
3RT2023 3RT2024 3RT2025 3RT2026 3RT2027 3RT2028
Size
S0
S0
S0
S0
S0
S0
General data
Degree of protection to EN 60947-1,
Annex C
IP20, drive system IP40
Touch protection acc. to DIN EN 50274
Finger-safe
AC operation
g/ms
7.5/5 and 4.7/10
8.3/5 and 5.3/10
Shock resistance
rectangular pulse
DC operation
g/ms
> 10/5 and > 7.5/10
AC operation
g/ms
11.8/5 and 7.4/10
13/5 and 8.3/10
Shock resistance
sine pulse
DC operation
g/ms
> 15/5 and > 10/10
Conductor cross-sections
2)
1)
Contact service life for main contacts is listed in the table titled "Contact service life of auxiliary and main contacts".
2)
Conductor cross-sections are listed in the table titled "Conductor cross-sections - 3RT202.".
Table 2- 85 Short-circuit protection for 3RT202. contactors without overload relay
Type
3RT2023 3RT2024 3RT2025 3RT2026 3RT2027 3RT2028
Size
S0
Short-circuit protection for contactors without overload relay
Main circuit
Fuse links gL/gG NH 3NA, DIAZED 5SB,
NEOZED 5SE acc. to
IEC 60947-4-1/DIN EN 60947-4-1
- Type of coordination "1"
A
63
100
125
- Type of coordination "2"
A
25
35
50
- Weld-free
1)
A
10
16
15
Miniature circuit breaker with C
characteristic (short-circuit current
3 kA, type of coordination "1")
A
25
32
40
Auxiliary circuit
Fuse links gL/gG DIAZED 5SB,
NEOZED 5SE (weld-free fuse
protection I
k
≥ 1 kA)
A
10
Miniature circuit breakers with C
characteristic (short-circuit
current I
k
< 400 A)
A
10
1)
Test conditions in accordance with IEC 60947-4-1.