![Siemens SIRIUS 3RH Series System Manual Download Page 467](http://html.mh-extra.com/html/siemens/sirius-3rh-series/sirius-3rh-series_system-manual_383139467.webp)
SIRIUS 3RV2 motor starter protectors
4.10 Technical data
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
467
4.10.11.3
Short-circuit breaking capacity for motor starter protectors with limiter function
Short-circuit breaking capacity for motor starter protectors with limiter function for 500 V AC and
690 V AC according to IEC 60947-2
The data for the short-circuit breaking capacity of motor starter protectors with limiter
function can be obtained on request on the Internet.
See also
Service & Support (
4.10.12
Permissible rated data of approved devices for North America (UL/CSA)
4.10.12.1
Approved according to UL 508/CSA C22.2 No. 14
The motor starter protectors in the 3RV2 series are approved for UL/CSA and can be used
conforming to UL 508 and CSA C22.2 No.14 individually or as load feeders in conjunction
with a contactor.
These motor starter protectors can be used as "Manual Motor Controller" for "Group
Installations", as "Manual Motor Controller Suitable for Tap Conductor Protection in Group
Installations", and as "Self-Protected Combination Motor Controller (Type E)".
Horsepower data
Voltage
115 V
200/208 V
230/240 V
460/480 V
575/600 V
Operating
current
1-phase 3-phase 1-phase 3-phase
1-phase 3-phase 1-phase 3-phase 1-phase 3-phase
3RV2011/3RV2111/3RV2311/3RV2411 size S00
0.11...0.1
6
-
-
-
-
-
-
-
-
-
-
0.14...0.2 -
-
-
-
-
-
-
-
-
-
0.18...0.2
5
-
-
-
-
-
-
-
-
-
-
0.22..0.32 -
-
-
-
-
-
-
-
-
-
0.28...0.4 -
-
-
-
-
-
-
-
-
-
0.35...0.5 -
-
-
-
-
-
-
-
-
-
0.45...0.6
3
-
-
-
-
-
-
-
-
-
-
0.55...0.8 -
-
-
-
-
-
-
-
-
-
0.7...1
-
-
-
-
-
-
-
-
-
1/2
0.9...1.25 -
-
-
-
-
-
-
1/2
-
1/2
1.1...1.6
-
-
-
-
1/10
-
-
3/4
-
3/4
Summary of Contents for SIRIUS 3RH Series
Page 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Page 2: ......
Page 785: ......